10 – APPENDIX
161
Starter Status Register:
Bit 0 – Ready 0 – Initializing or
Faulted and Decelling or
Faulted and Braking or
Faulted and Stopped or
Lockout
1 – Otherwise
Bit 1 – Running 0 – Not Running
1 – Running
Bit 2 – UTS 0 – Not UTS
1 – UTS
Bit 3 – Alarm 0 – No alarm conditions
1 – 1 or more alarm conditions
Bit 4 – Fault 0 – No Fault Condition
1 – Fault Condition
Bit 5 – Lockout 0 – Start or Fault Reset not locked out.
1 – Start or Fault Reset locked out. Possible causes are:
Overload Lockout State
Parameter Registers:
For those parameters that can be set either to “Off”, or some value within a range (many of the protection parameters, for example)
there are two Modbus registers. One is an “enable” register, and the other sets the value within the range.